Standard UL labeled NEMA 1 enclosure contains 600-ampere,
three-phase, copper tin-plated horizontal main bus, 300-ampere,
three-phase, copper tin-plated vertical bus and is braced to
withstand a fault current of 65,000 rms symmetrical. Each vertical
section must be priced to include 72 inches of vertical space
units consisting of starters, feeders, transformers, panels, incoming
terminal boards and/or enclosure spaces for future units.
1Typical diagrams can be found in the Application and Selection Guide for DET291
Section “L”.
Motor Control Centers
3
3-4 Aftermarket Catalog
www.geelectrical.com Prices and data subject
to change without notice
Motor Control Centers—Low Voltage
GE Motor Control Centers
EVOLUTION SERIES E9000? Key Benefits
Safety:
—No Hot bus rework up to 600A
—Hi-Visible Trip Indication
—Door and unit interlocks
—UBC Seismic Zone 4 Standard
—Six Sigma Designed
Size:
—6" reduction—Sz 3, 5
—6" to 36" reduction VFD’s
—6" Size 1 FVNR
—6" 150A Feeder
—12" 250A Feeder
—36" Size 5 Plug-In, two in a section
—300VA CPT—No additional Space
—Plug In Buckets to Size 5
—Plug In Feeders to 600A
Simplicity:
—Easy Unit Insertion/Removal
—Snap-In Shelves
—Easily Quoted… Fastrac MCCs
—Manufacturing Flexibility
Scope:
—450 Hp VFD’s
—500 Hp SSS
—250A and 600A Stabs
—TVSS 65-200K Surge Current
—Automatic Transfer Switches to 1200A
Motor Control Centers
3
Prices and data subject Aftermarket Catalog
www.geelectrical.com 3-5
to change without notice
Motor Control Centers—Low Voltage
GE Motor Control Centers
Short/Mid Cycle Program
Features
The Evolution SC/MC is a pre-engineered, factory assembled, fully
tested motor control center that contains all the standard features
of the Evolution motor control center, including some
options.
All sections and units will be UL labeled where possible. Refer to
Company if labeling is critical.
Please contact your distributor or GE for scope, pricing, and
ordering.
No changes are allowed to Evolution SC/MC bill-ofmaterial
after order entry.
Highlights of the Evolution SC/MC Program:
I Structure (20-inch wide is standard)
—13- or 20-inch deep
—Back-to-back mounting (20-inch deep only)
—NEMA 1 gasket, 2, 12, 3R non-walk-in
—24-inch wide enclosures
—Corner section enclosures
—Special enclosures
—Engraved nameplates (optional)
—Addition of “Field Installed Kits”
II Bus Systems
—Voltage: 208, 240, 480, 575 volts
—3-phase, 3-wire, or 3-phase, 4-wire
—Main bus: 600, 800, 1000, 1200 ampere
—Vertical bus: 300, 450, 600 ampere, section-by-section
—Optional ground bus: 300, 375, 600 ampere
—Neutral bus: 300, 400, 600, 800, 1000 ampere
—Optional silver plating
—Back-to-back construction (rear vertical bus)
—“Vertical Bus Plugs” installed in unused stab openings
III Incoming Line
—600 amperes with 18 inches of pull space
—Circuit breakers thru 1200 amperes
—Fusible switches thru 600 amperes
IV Feeders and Mains
—Feeders—800-ampere Spectra
—Feeders—600-ampere fused switch
—Main—1200-ampere Spectra
—Shunt trip and UV release
V Combination Starter Units
—Control Power Transformer (CPT) (optional)
—“Extra” auxiliary interlocks (optional)
—Line-to-line control
—Line-to-neutral control
—Separate control power or common CPT
—FVNR—Size 1 thru 6
—FVR—Size 1 thru 4
—RVNR—Size 2 thru 5
—2S2W—Size 1 thru 4
—2S1W—Size 1 thru 4
—NEMA Type 1B wiring
—Interlocks mounted on circuit breaker and
fusible switch (optional)
Motor Control Centers
3
3-6 Aftermarket Catalog
www.geelectrical.com Prices and data subject
to change without notice
Motor Control Centers—Low Voltage
Frequently Requested Motor Control Center Renewal Parts
EVOLUTION SERIES E9000?
Renewal Parts List Price
Part Description Product Number GO-11GM
Size 1 Standard O/L 9000RSG1 緯軒機(jī)電87.00
Size 1 Electronic O/L 9000RSG2 緯軒機(jī)電87.00
O/L Reset Assembly Size 2,5 Standard O/L 9000RSG3 緯軒機(jī)電87.00
Size 2,5 Electronic O/L 9000RSG4 緯軒機(jī)電87.00
Size 3,4 Standard O/L 9000RSG5 緯軒機(jī)電87.00
Size 3,4 Electronic O/L 9000RSG6 緯軒機(jī)電87.00
Door Hinges Door Hinges 190B1013P1 緯軒機(jī)電9.00
Power Pull Apart Terminal Block 50A 190B1691G1 緯軒機(jī)電84.00
Terminal Block Din Rail Assembly 18 Points Max 190B2070G6 緯軒機(jī)電309.00
Terminal Blocks Terminal Block Din Rail Assembly 18 Points Max w/ TB 190B2070G12 緯軒機(jī)電534.00
Control TB 30A Male and Female 190B1692G1 緯軒機(jī)電45.00
Wireway Covers Top 12" with hinges 110C1440G1 緯軒機(jī)電170.00 Wireway Covers Wireway Covers Top 18" with hinges 110C1440G2 緯軒機(jī)電204.00
CPT 150VA, 480/120 Size 1 and 2 w/o Fuse Block 9T58K0504G37 緯軒機(jī)電310.001
Control Power Transformers CPT 300VA, 480/120 Size 1 and 2 With Fuse Block 9T58K0507G38 緯軒機(jī)電390.001
CPT 100VA, 480/120 Size 1 1/2X, Size 5 W/O Fuse Block MIC#B100-2989-5 緯軒機(jī)電240.00
Standard Shelf 110C1059P1 緯軒機(jī)電144.00
Shelf Grounding Bracket 270A1343G1 緯軒機(jī)電18.00
Miscellaneous Bus Shutter Assembly 110C1783G1 緯軒機(jī)電346.00
Vertical Bus Stab Covers 190B1215P1 緯軒機(jī)電9.00
Wireway Knock Out Panel 190B1014P1 緯軒機(jī)電12.00
Shelf Support - 72" High 110C1010G11 緯軒機(jī)電310.00
Circuit Breaker/Starter Handles E and F Frame CB Vertical Handle Only 190B1704G1 緯軒機(jī)電120.00
E and F Frame CB Horizontal Handle Only 190B1704G2 緯軒機(jī)電120.00
6" EK06 緯軒機(jī)電120.002
12" EK12 緯軒機(jī)電240.002
18" EK18 緯軒機(jī)電490.00
Filler Kits 24" EK24 緯軒機(jī)電505.00
(Includes Shelf and Grounding Bracket) 30" EK30 緯軒機(jī)電575.00
36" EK36 緯軒機(jī)電610.00
42" EK42 緯軒機(jī)電640.00
48" EK48 緯軒機(jī)電680.00
Rear Cover Only 190B1007P9 緯軒機(jī)電114.00
Rear Doors Only Rear Hinge Door Top Only 110C1466G9 緯軒機(jī)電132.00
Rear Hinge Door Bottom Only 110C1466G21 緯軒機(jī)電132.00
Rear Hinge Mounting Bracket (2 Per Section) 110C1464P1 緯軒機(jī)電14.00
6" High 110C1163G1 緯軒機(jī)電260.00
12" High 110C1163G2 緯軒機(jī)電332.80
18" High 110C1163G3 緯軒機(jī)電353.60
24" High 110C1163G4 緯軒機(jī)電374.40
30" High 110C1163G5 緯軒機(jī)電396.00
Wire Trough Doors (4") 36" High 110C1163G6 緯軒機(jī)電416.00
42" High 110C1163G7 緯軒機(jī)電426.40
48" High 110C1163G8 緯軒機(jī)電426.40
54" High 110C1163G9 緯軒機(jī)電457.60
60" High 110C1163G10 緯軒機(jī)電478.40
66" High 110C1163G11 緯軒機(jī)電499.20
72" High 110C1163G12 緯軒機(jī)電572.00